Configure a maintenance monitoring mode – Rockwell Automation 1752-L24BBBE SmartGuard 600 Controllers User Manual User Manual
Page 173
Advertising

Rockwell Automation Publication 1752-UM001E-EN-P - June 2014
173
Monitor Status and Handle Faults
Chapter 12
Configure a Maintenance Monitoring Mode
Follow these steps to configure contact operation counter mode for a terminal.
1.
In RSNetWorx for DeviceNet software, right-click the controller and
choose Properties.
2.
Select the Maintenance tab.
3.
Select the Local Input, Local Output, or Test Output tab.
EXAMPLE
ATTENTION: Calculating Total On-time With 1.5 Second On
Pulses
ATTENTION: In this example, the bit is actually on for 1.5 s x 2 = 3 s, but
the bit is on 4 times when status is checked, so the total on-time is
measured as 4 s.
1.5 s
Measured 1 Time/Second
ON
OFF