Chapter 7 Troubleshoot the Controller

A force overrides a value from an input device or logic.

• Forcing an input tag overrides the value from the input device.

• Forcing an output tag overrides your logic and sends the force value to the output device.

When forces are in effect (enabled), a appears next to the forced element.

The force indicator on the front of the controller and in the programming software indicates status.

If you want to

Then

Override a value

Install an I/O force (force an I/O value)

Stop an individual force but leave other forces enabled and in effect Remove an individual force

Stop all I/O forces but leave the I/O forces in the project

Disable all I/O forces

If the indicator is

Then

Off

• No tags contain I/O force values.
• I/O forces are inactive (disabled).

Flashing amber

• One or more tags contain a force value.
• I/O forces are inactive (disabled).
• When you enable I/O forces, all existing I/O forces take effect.

Solid amber

• I/O forces are active (enabled).
• Force values may or may not exist.
• When you install (add) a force, it immediately takes effect.