NOTICE

Please note that all parameters are set to their default values on delivery.

Please check all the safety­related parameters at least, and enter the values
that correspond to your application.

6.2.3

Password protection

The configuration is password­protected.

}

Parameters can only be changed once a password has been entered.

}

Factory setting for the password: 000000

}

The pasword consists of 6 figures in the range 000000 … 999999.

}

The password can be changed at any time in the menu.

INFORMATION

– Please note: Remember the assigned password. Without this pass­

word you will not be able to change the configuration.

– For details of how to enter the password, see the section entitled

"Status display and configuration", Level 2: Entering the password.

– For details of how to change the password, see the section entitled

"Status display and configuration", Level 3: Configuration.

6.2.4

Use chip card

The parameters that are set on a device are stored on the chip card. The data is stored
along with a device identifier and check sum. We recommend that you always operate the
device with a chip card.

When the chip card is inside the device:

}

The chip card is checked to verify the device identifier, valid parameters, and ensure
that the data is identical.

}

Device parameters are automatically saved to the chip card during configuration. As a
result, the chip card always contains a copy of the device's current internal data.

When the device is switched on in the Power On operating state (all LEDs illuminate
briefly) a test is carried out to check whether

}

a chip card is inserted or just an empty chip card holder

}

data on the chip card matches the data in the device

}

data on the chip card is valid.