Carrier 50HCQ04---12 User Manual

Page 15

Advertising
background image

15

Vent Dmpr Pos / DCV Min Pos – Minimum damper

position for ventilation during the occupied period

Range = 95-150_F

Default = 120_F

DCV Max Vent Damper Pos – This is the greatest

position the economizer can open to while trying to

control the indoor air quality levels

Range = 10-60%open Default = 50%open

S Fan Service Alarm Timer – The timer set for the

Supply Fan Runtime Alarm. After the number of hours

set on this point is exceeded the corresponding alarm will

be generated, and must be manually cleared in the

maintenance menu after the maintenance has been

completed. The timer will then begin counting its runtime

again for the next due maintenance.
NOTE: Default = 0 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Comp 1 Service Alarm Timer – The timer set for the

Compressor 1 Runtime Alarm. After the number of hours

set on this point is exceeded the corresponding alarm will

be generated, and must be manually cleared in the

maintenance menu after the maintenance has been

completed. The timer will then begin counting its runtime

again for the next due maintenance.
NOTE: Default = 0 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Comp 2 Service Alarm Timer – The timer set for the

Compressor 2 Runtime Alarm. After the number of hours

set on this point is exceeded the corresponding alarm will

be generated, and must be manually cleared in the

maintenance menu after the maintenance has been

completed. The timer will then begin counting its runtime

again for the next due maintenance.
NOTE: Default = 0 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Filter Service Alarm Timer – The timer set for the Dirty

Filter Alarm. After the number of hours set on this point

is exceeded the corresponding alarm will be generated,

and must be manually cleared in the maintenance menu

after the maintenance has been completed. The timer will

then begin counting its runtime again for the next due

maintenance.
NOTE: Default = 600 hours, if set = 0 hr this point is
disabled and its alarm will never be generated.
Pushbutton Override – Set to enable or disable the

pushbutton override function of the locally installed space

sensor.

Default = Enable
Setpoint Adjustment – Set to enable or disable the

setpoint adjustment function of the locally installed space

sensor.

Default = Enable
Setpoint Adjustment Range -- Sets the slider range of a

space sensor (with built in function). The slider is used to

offset the control setpoint.

Range = +/-0-5n_F

Default = 5n_F

Cooling Lockout Temperature -- This defines the

minimum outdoor air temperature that cooling mode can

be enabled and run. If the OAT falls below this number

during cooling the compressors will be de-energized.

Range = 0-80_F

Default = 45_F

Economizer High OAT Lockout Temp – If the outdoor

air temperature rises above this value, economizer cooling

will be disabled and dampers will return and stay at

minimum position.

Range = 55-80_F

Default = 75_F

HP Rev Cycle Lockout Temp – If the outdoor air

temperature falls below this value, the compressors will

not be allowed to run for heating. Unit Type must be set

to Heat pump for this to be active.

Range = -20-30_F

Default = -3_F

Heating Lockout Temperature – This defines the

maximum outdoor air temperature that heating mode can

be enabled and run. If the OAT rises above this number

during heating the heat stages will be de-energized.

Range = 35-150_F

Default = 65_F

Unocc Free Cool Enable – Set to enable or disable the

economizer for night time free cooling (NTFC) operation.

Default = Disable
Setpoint Separation – Sets the minimum separation gap

in which setpoints can be set.

Range = 2-10_F

Default = 5_F

Occupancy Source – Tells the controller which method of

occupancy control to use in determining occupancy of the

rooftop. Refer to Occupancy in the operation section for

detail on each specific operation function.

Range = Always Occupied, BACnet Schedule,

BAS On/Off, or Remote Occ Input

Default = Always occupied

Inputs

Input 1 Function – This input is an analog input and can

be configured to be one of four different inputs: No

Sensor, IAQ Sensor, OAQ Sensor, or Space RH Sensor.

Input 1 is wired to pin J4-5.

Default = No Sensor
Input 2 Function – This input is an analog input and can

be configured to be one of four different inputs: No

Sensor, IAQ Sensor, OAQ Sensor, or Space RH Sensor.

Input 2 is wired to pin J4-2.

Software Default = No Sensor

Factory Default = IAQ Sensor with factory installed CO

2

sensor
Input 3 -- This input is a discrete input and can be

configured to be one of six different functions: No

Function, Compressor Safety, Fan Status, Filter Status,

Remote Occupancy, or Door Contact. This input can also

be configured to be either a Normally Open (N/O) or a

Normally Closed (N/C) switch. Input 3 is factory wired to

pin J1-2. Field accessories can be wired to its parallel pin

J5-5.

Factory Default = Compressor Safety and N/O