Configuration points (con’t) – Carrier 50HCQ04---12 User Manual

Page 43

Advertising
background image

43

CONFIGURATION POINTS (CON’T)

BACview

MENU

POINT NAME

BACnet

OBJECT

RANGE

DEFAULT

ENTRY

HOME

Select function below

CONFIG

CONFIGURATION

INPUT

INPUT CONFIGURATION

Input 1 Function

ai1_function

1=No Sensor

2=IAO Sensor

3=OAQ Sensor

4=Space RH

Sensor

No Sensor

Input 2 Function

ai2_function

1=No Sensor

2=IAO Sensor

3=OAQ Sensor

4=Space RH

Sensor

1 (No FIOP)

2 (FIOP)

Input 3 Function

di3_function

1=No Function

2=Compressor

Safety

3=Fan Status

4=Filter Status

5=Remote Occu-

pancy

6=Door Contact

Compressor Safety

Input 3 Switch Configuration

di3_type

N/O

N/C

N/O

Input 5 Function

di5_function

1=No Function

2=Fire Shutdown

3=Fan Status

4=Filter Status

5=Remote Occu-

pancy

6=Door Contact

Fire Shutdown

Input 5 Switch Configuration

di5_type

N/O

N/C

N/O

Input 8 Function

di8_function

1=No Function

2=Enthalpy Switch

3=Fan Status

4=Filter Status

5=Remote Occu-

pancy

6=Door Contact

1 (No FIOP)

2 (FIOP)

Input 8 Switch Configuration

di8_type

N/O

N/C

N/O

Input 9 Function

di9_function

1=No Function

2=Humidistat

3=Fan Status

4=Filter Status

5=Remote Occu-

pancy

6=Door Contact

Humidistat

Input 9 Switch Configuration

di9_type

N/O

N/C

N/O

Space sensor type

spt_type

1=T55

2=T56 (use for T59)

3=SPT Sensor

T55

T5x Override Duration

ovr_dur

0---24 hours

1