Installing discrete inputs – Carrier 50HCQ04---12 User Manual

Page 8

Advertising
background image

8

Relative Humidity Sensors (Space or Duct

Mounted)

The accessory space humidity sensor or duct humidity

sensor is used to measure the relative humidity of the air

within the space or return air duct. The RH reading is used

to control the Humidi-Mizert option of the rooftop unit.

For wiring distances up to 500 ft (152m), use a

3-conductor, 18 or 20 AWG shielded cable. The shield

must be removed from the sensor end of the cable and

grounded at the unit end. The current loop power for the

sensor is provided by the RTU-OPEN controller as 24vdc.

Refer to the instructions supplied with the RH sensor for

electrical

requirements

and

terminal

locations.

RTU-OPEN configurations must be changed after adding

a RH sensor. See below and Fig. 8 and 9 for typical RH

sensor wiring.

S

J4--1 or J4--4 = 24vdc loop power

S

J4--2 or J4--5 = 4--20mA signal input

NOTE: The factory default for dehumidification control
is a normally open humidistat.

Installing Discrete Inputs

Compressor Safety

The compressor safety input provides the RTU-OPEN

with feedback to when the compressor is not running and

should be.

This feedback is usually provided by a

Compressor Lock-Out (CLO) device. Compressor safety

is a dedicated input on the configurable input 3 and tells

the RTU-OPEN when the compressor is locked out. The

normal condition for compressor safety is good operation.

A normally open compressor safety is the factory default

for all units. Follow specific accessory instructions if

installing a CLO device. The CLO should wire into the

unit’s Low Voltage terminal Board (LVTB).
NOTE: Input 3 can also be wired into J--5.

SW2

1

2

3

4

5

6

ON

Io

Vin

Gnd

Vo

MOUNTING
HOLES

WIRING
OPENING

a33-9141

Vin - J4 -1 or J4 -4 24Vdc
Io - J4 -2 or J4 -5 4 -20mA output

C07201

Fig. 8 -- Space Relative Humidity Sensor Typical Wiring

Humidistat

The accessory humidistat provides the RTU-OPEN insight

to the relative humidity in the space. The humidistat

reads the RH level in the space and compares it to its

setpoint to operate a dry contact. The humidistat is a

dedicated input on the configurable input 9 and tells the

RTU-OPEN when the RH level is HIGH or LOW. The

normal condition for humidity is LOW. A normally open

humidistat is the factory default control for the

Humidi-MiZert option. To wire in the field:

S

J5--8 = 24 VAC source for dry contact

S

J5--7 = Signal input

Single Enthalpy (Outdoor Enthalpy)

The outdoor enthalpy switch/receiver (33CSENTHSW)

senses temperature and humidity of the air surrounding

the device and calculates the enthalpy when used without

an enthalpy sensor. The relay is energized when enthalpy

is high (above 28 BTU/lb OR dry bulb temperature is

above 75_F) and de-energized when enthalpy is low

(below 27 BTU/lb AND dry bulb temperature is below

74.5_F). The enthalpy input is dedicated to input 8 and

tells the RTU-OPEN when the outside air enthalpy is

HIGH or LOW. The normal condition for the enthalpy

input is HIGH. Enthalpy is configured on input 8 in the

factory when it is added as an option.
NOTE:

The enthalpy calculation is done using an

average altitude of 1000 ft above sea level.
For field installation, refer to the enthalpy accessory

instructions. For wiring see below and Fig. 10. The

RTU-OPEN board provides 24vac on one of the two loose

grey wires in the return air section of the rooftop near the

12-pin economizer plug. To determine the correct grey,

measure the voltage on the wires with power applied to

the unit. If 24-vac is sensed, then that is the grey wire that

is connected to the RTU-OPEN board at J2-7. The other

is the signal for input 8, connect it to the LOW Enthalpy

terminal on the enthalpy switch/receiver. Tie into the

12-pin economizer plug on pin 4 or the black wire

connected to the actuator for the enthalpy’s GND

connection. Power can also be provided direct from the

unit transformer and J5 terminal on the RTU-OPEN.

S

J2--7 or J5--2 = 24 VAC for enthalpy switch power

S

J2--6 or J5--1 = input signal

Differential Enthalpy

Differential enthalpy control requires both an enthalpy

switch/receiver (33CSENTHSW) and an enthalpy sensor

(33CSENTSEN). The enthalpy sensor must be installed

in the field as the factory can only provide single

enthalpy. The enthalpy sensor must be mounted in the

return airstream and calculates the enthalpy of the indoor

air. The relay is energized when the enthalpy detected by

the return air enthalpy sensor is less than the enthalpy at

the enthalpy switch/receiver. The relay is de-energized

when the enthalpy detected by the return air enthalpy

sensor is greater than the enthalpy at the enthalpy

switch/receiver (differential enthalpy control).

Advertising
This manual is related to the following products: