8 configuration, Configuration, Configu – Pilz PSSu K F FCU User Manual

Page 18: Ration

Advertising
background image

Function description

Operating Manual PSSu K F FCU
1002391-EN-04

18

Processing time of the inputs without fast shutdown for a configured input filter time

Input

PII

t

2

+t

3

t

t

1

t

1

t

2

+t

3

t

1

}

Input: Signal at the input

}

PII: Status of process image (PII)

}

t

1

Safely filtered out signal time (see table in the chapter entitled "Configuration")

}

t

2

Maximum processing time of the input (see Technical details)

}

t

3

Cycle time of module bus

Shaded area: Status of process image (PII) undefined.
t

Max. processing time for input

= (t

configured input filter time

+

2.50 ms)

You can find the processing time of the outputs in the technical data.

Configuration

The module has the following configuration options:
Outputs

}

Deactivate fast shutdown for individual outputs

Default value:
The fast shutdown is activated for all outputs

}

Output test for single-pole outputs

Default value:
The output test is activated for all single-pole outputs
Inputs:

}

Test pulses

Default value:
The test pulses are activated for all inputs

}

Edge used to trigger the fast shutdown

Default values:
Inputs for fast shutdown:

– I00 ... I07: Fast shutdown with falling edge

}

Filter times (default: 300 µs)

The input filter time can be configured separately for inputs with and without fast shutdown.
The input filter time can be configured in increments of 100 µs. The input filter time depends
on the edge configured for fast shutdown. For each input filter time that is configured, there
are two values each for the rising and the falling edge:

4.8