Basler Electric BE1-700 User Manual
Page 197
Output
Purpose
Output Description
Label
State Labels
TRUE
FALSE
VO5
(OUT5)
Major Alarm
Closes contact when Major Alarm
expression is TRUE
ALMMAJ
Active
Normal
BESTlogic expression: VO5=ALMMAJ
VO6
Not used
VO6
True
False
BESTlogic expression: VO6=0
VO7
Not used
VO7
True
False
BESTlogic expression: VO7=0
VO8
Reclose Initiate
TRUE when any protective
element trips or when the external
reclose initiate input is TRUE.
RCL_INI
INI
Normal
BESTlogic expression: VO8=VO11+IN3
VO9
Recloser Drive to Lockout Drive recloser to lockout if IN2 is
energized or the high-set
instantaneous elements trip.
RCL_DTL
DTL
Normal
BESTlogic expression: VO9=150TPT+150TNT+15OTQT+/IN2
VO10
Not used
VO10
True
False
BESTlogic expression: VO10=0
VO11
Protective Trip
Expression
TRUE when any 50, 150 or 51
element has timed out.
PROT_TRIP
Trip
Normal
BESTlogic expression: VO11=50TPT+150TPT+50TNT+150TNT+50TQT+150TQT+51PT+51NT+51QT
VO12
Protection Picked Up
Expression
TRUE when any 50, 150 or 51
element has picked up.
PROT_PU
PU
Normal
BESTlogic expression:
VO12=50TPPU+150TPPU+50TNPU+150TNPU+50TQPU+150TQPU+51PPU+51NPU+51QPU
VO13
Alarm Mask 21
VO13
True
False
BESTlogic expression: VO13=0
VO14
Alarm Mask 22
VO14
True
False
BESTlogic expression: VO14=0
VO15
Alarm Mask 23
VO15
True
False
BESTlogic expression: VO15=0
9376700990 Rev M
BE1-700 Application