Figure 8-10. 700V-VF79-A-BE (V & F Protection with Reclosing) One-Line Drawing
Table 8-16. 700V-VF79-A-BE (V & F Protection with Reclosing) Contact Sensing Input Logic
Input
Purpose
Label
State Labels
Energized
De-Energized
IN1
Breaker status indication in Sequence of
Events Reporting. TRUE when breaker is
open. Typically, IN1 is connected to the 52b
contact of the breaker.
BREAKER
OPEN
CLOSED
IN2
Reclosing Drive to Lockout. Drives recloser
to lockout when external switch is turned off.
Contact from external switch must be closed
in the off position, open in the on.
REC_OFF
OFF
ON
IN3
External time delay reclose initiate. TRUE
when RI is high.
EXT_RI
ACTIVE
NORMAL
IN4
External high speed (pilot) reclose initiate.
TRUE when PI is high.
EXT_PI
ACTIVE
NORMAL
Table 8-17. 700V-VF79-A-BE (V & F Protection with Reclosing) Function Block Logic
Function
Purpose
BESTlogic
Expression
Mode Setting
24
Used for detection of transformer overexcitation
0
1 (enabled)
25
(25VM)
Blocked when 79C is FALSE (/79C) or when 79LO is
TRUE. Set 25VM Hot Bus-Dead Line
/79C+79LO
1 (enabled)
8-26
BE1-700 Application