Breaker monitor setting commands, General setting commands, Breaker monitor setting commands -14 – Basler Electric BE1-700 User Manual
Page 260: General setting commands -14
SA-MAJ Command
Purpose:
Read/Set major alarm setting mask
Syntax:
SA-MAJ[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MAJ or SA-MAJ=1/3/5/12
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
SA-MIN Command
Purpose:
Read/Set minor alarm setting mask
Syntax:
SA-MIN[={alarm num 1}[/{alarm num 2}]...[/{alarm num n}]]
Example:
SA-MIN or SA-MIN=2/6/7/10/11
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
SA-RESET Command
Purpose:
Read/Set Programmable Alarms Reset logic
Syntax:
SA-RESET[={rst alm logic}]
Example:
SA-RESET or SA-RESET=VO1
Reference:
Section 6, Reporting and Alarm Functions, Alarms Function
Breaker Monitor Setting Commands
SB Command
Purpose:
Read all breaker settings
Syntax:
SB
Example:
SB
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
SB-DUTY Command
Purpose:
Read/Set Breaker Contact Duty where mode = 0/1/2 (disabled/I/I^2)
Syntax:
SB-DUTY[={mode},{dmax},{BLKBKR logic}]
Example:
SB-DUTY=1,60E3,IN5
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
SB-LOGIC Command
Purpose:
Read/Set Breaker Contact Logic
Syntax:
SB-LOGIC[={breaker close logic}]
Example:
SB-LOGIC=IN1 (IN1=52a) or SB-LOGIC=/IN2 (IN2=52b)
Reference:
Section 6, Reporting and Alarm Functions, Breaker Monitoring
General Setting Commands
SG Command
Purpose:
Read all general settings
Syntax:
SG
Example:
SG
Reference:
Section 11, ASCII Command Interface, Settings (S) Command Descriptions
SG-BL Command
Purpose:
Read/Program backlight timer
Syntax:
SG-BL[={timer}]
Example:
SG-BL=5000 or SG-BL=60000
Reference:
Section 10, Human-Machine Interface, Front Panel Display, Backlight Timer
11-14
BE1-700 ASCII Command Interface
9376700990 Rev M