Basler Electric BE1-700 User Manual
Page 211
Output
Purpose
Description
Label
State Labels
VO6
Not used
VO6
True
False
BESTlogic expression: VO6=0
VO7
Not used
VO7
True
False
BESTlogic expression: VO7=0
VO8
Not used
VO8
True
False
BESTlogic expression: VO8=0
VO9
Sync-Check Close
79C is TRUE and 25 is
TRUE
SYNC_
CLOSE
Close
Normal
BESTlogic expression: VO9=79C*25
VO10
Conditional Voltage Close
79C is TRUE and 25VM1
is TRUE
VOLT_
CLOSE
Close
Normal
BESTlogic expression: VO10=79C*25VM1
VO11
Protective trip expression
VO11 is TRUE when any
OC&P or V&F protection
element trips
PROT_TRIP
Trip
Normal
BESTlogic expression:
VO11=24T+27XT+27PT+127PT+47T+59PT+159PT+59XT+159XT+81T+181T+281T+381T+481T+581T
VO12
Protective pickup
expression
VO12 is TRUE when any
protection element picks up
PROT_PU
PU
Normal
BESTlogic expression: VO12=24PPU+27XPU+27PPU+127PPU+47PU+59PPU+159PPU+59XPU +159XPU +81T
+181T +281T+381T+481T+581T
VO13
Pilot Reclose Initiate
VO13 is TRUE when IN1,
is TRUE
PILOT_INI
INI
Normal
BESTlogic expression: VO13=IN1
VO14
Reclose Initiate
VO14 is TRUE when IN3
or VO13 is TRUE
REC_INI
INI
Normal
BESTlogic expression: VO14=IN3+VO13
VO15
Alarm Mask 21
VO15
True
False
BESTlogic expression: VO15=0
9376700990 Rev M
BE1-700 Application