Bestlogic, General specifications, Ac current inputs (be1-700c) – Basler Electric BE1-700 User Manual
Page 23: Phase ac voltage inputs (be1-700v), Auxiliary ac voltage inputs, Analog to digital converter, Power supply, Bestlogic -11, General specifications -11, Ac current inputs (be1-700c) -11
BESTlogic
™
Update Rate:
½ cycle
GENERAL SPECIFICATIONS
AC Current Inputs (BE1-700C)
5 Ampere CT
Continuous Rating:
20 A
One Second Rating:
400 A
For other current levels, use the formula: I= (K/t)
½
where t = time in seconds, K = 160,000.
Begins to Clip (Saturate):
150 A
Burden:
<0.01
Ω
1 Ampere CT
Continuous Rating:
4 A
One Second Rating:
80 A
For other current levels, use the following formula: I = (K/t)
½
where t = time in seconds, K = 90,000 (panel
mount, non-drawout case).
Begins to Clip (Saturate):
30 A
Burden:
≤0.01 Ω at 1 A
Phase AC Voltage Inputs (BE1-700V)
Continuous Rating:
300 V, Line to Line
One Second Rating:
600 V, Line to Line (3-wire sensing)
600 V, Line to Neutral (4-wire sensing)
Burden:
<1 VA at 300 Vac
Auxiliary AC Voltage Inputs
Continuous Rating:
150 V, Line to Line
Fault Rating:
360 V, Line to Line
One Second Rating:
600 V, Line to Neutral
Burden:
<1 VA at 150 Vac
Analog to Digital Converter
Type:
16-bit
Sampling Rate:
12 samples per cycle, adjusted to input frequency
(10 to 75 Hz)
Power Supply
Power supply ranges and holdup times are listed in Table 1-1.
Table 1-1. Power Supply Ranges and Holdup Times
Style Option
AC Range
AC Holdup Time
DC Range
DC Holdup Time
1) 48 Vdc
N/A
N/A
35 to 150 Vdc
30 ms
2) 125 Vac/dc
90 to 270 Vac
70 ms
90 to 300 Vdc
50 ms
3) 24 Vdc
N/A
N/A
17 to 32 Vdc †
80 ms
4) 250 Vac/dc
90 to 270 Vac
280 ms
90 to 300 Vdc
170 ms
5) 125 Vac/dc
* 55 to 135 Vac
280 ms
35 to 150 Vdc
170 ms
* Extended holdup option. See Style Chart in Figure 1-1.
† Operates down to 8 Vdc momentarily.
9376700990 Rev M
BE1-700 General Information
1-11