Cpu board – Gasboy CFN Site Controller User Manual

Page 35

Advertising
background image

Pump Interface Manual v1.3

Gilbarco Interface Unit

27

03/20/03

Gasboy CFN Series

CPU Board

DIP Switch Bank 2. This switch sets the poll address and allows memory to be cleared.

DIP Switch Bank 3

All positions are normally OPEN.

Jumper

Function and/or Normal Setting

K1

All K1 jumpers are absent.

K2

All K2 jumpers are absent.

K3

Position 1: enables the dead man timer.
K3-1 jumper must be installed.
K3-1 is the pair of K3 terminals closest to P9, the long double-row offboard
connector at the edge of the board.
Position 2: K3-2 jumper is absent. K3-2 is the pair of K3 terminals farthest from P9.

K4

____

K5

Battery to U31; must install.

K6

Battery to U32; must install.

K7

Enables the AC power fail circuit; must install.

K8

K8 jumper is absent.

Position & Definition

Setting(*=customary)

1

debug mode

*closed=normal mode
open=debug mode

2

erase memory on reset

*closed=no
open=yes

3-8

interface address

see below

Address

2-3

2-4

2-5

2-6

2-7

2-8

1

cl

cl

cl

cl

cl

cl

2

cl

cl

cl

cl

cl

op

3

cl

cl

cl

cl

op

cl

4

cl

cl

cl

cl

op

op

5

cl

cl

cl

op

cl

cl

.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

.

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

64

op

op

op

op

op

op

Position & Definition

Setting(*=customary)

1-2

local terminal baud rate

*open=9600
(also see below)

3

CRIND

*open=RS-422/485 to CRIND
closed=current loop

4

reports (see below)

open=onhook activate
closed=no report

5

allow product
authorization

OPEN = No grade restrictions
CLOSED = Restrict grades

6

money amounts

OPEN = Money amounts are five digits
CLOSED = Money amounts are six digits

7-8

reserved