Pump Interface Manual v1.3

Islander II

37

03/20/03

Gasboy CFN Series

Splitter Cabling

NOTES:

1.

Use a C05578 cable for connection to a single 67 or 98 Interface box. Use a
C05876 cable for connection to two 67 or 98 Interface boxes. Both cables include
the Tokheim Splitter.

2.

A Model 180 signal cable extension is available as an accessory from Tokheim.

The maximum distance of the combined cables and field wiring should not exceed
350 feet. The maximum distance for a 98 Interface box is 250 feet.

3.

Use part number C06694 for connection to three or more 98 Interface boxes.

C06694 is the combination of one C05878 cable, two C05577 cables and a
Tokheim Splitter.

4.

Communication for pumps 1-32 may be provided through port 1 or 3 of the

Islander II.

5.

The second two 98 boxes must be connected to channel 2 of the splitter. Address

the third 98 box (first 98 box on channel 2) as pumps 1 to 8; address the fourth 98
box (second 98 box on channel 2) as pumps 9 to 16.

WIRING TO PORT 1

OR PORT 3

TOKHEIM SPLITTER

C05578 OR C05876

APPROX. 12 FT. CABLE

(SEE NOTE 1)

APPROX. 12 FT. CABLE

FROM COMPUTER MODULE

(SEE NOTE 2)

CONNECTOR OR

TERM. BOX

MODEL 67/98

INTERFACE BOX

MODEL 67/98

INTERFACE BOX

WIRING TO PORT 1

OR PORT 3

C05851

TOKHEIM

SPLITTER

C05878

APPROX 1 FT.

CABLE

C05577

APPROX 12 FT. CABLE

C05577

APPROX 12 FT. CABLE

APPROX. 12 FT. CABLE

FROM COMPUTER MODULE

(SEE NOTE 2)

APPROX. 12 FT. CABLE

FROM COMPUTER MODULE

(SEE NOTE 2)

CONNECTOR OR

TERM. BOX

MODEL 98 SERIES

COMPUTER MODULE

PUMPS 1-8

MODEL 98 SERIES

COMPUTER MODULE

PUMPS 9-16

PUMPS 17-24

PUMPS 25-32

MODEL 98 SERIES

COMPUTER MODULE

MODEL 98 SERIES

COMPUTER MODULE

SEE

NOTE

5

CHANNEL

1

CHANNEL

2

(SEE NOTE 3)