INSTALLATION (cont.)

Ducting With Typical Drop Ceiling

All hardware is field supplied.

CAUTION: Do not operate the unit without the filter installed on the

return air grill.

1. Use a 12 inch diameter insulated duct with low friction and air resistance.

The duct should be bent in a large radius. If the bending radius is less than

15.0 inch (381 mm), then use vanes or guides to reduce air resistance.

2. Make sure the ducts are secured in order to absorb vibration from the unit.

Avoid sharp bending on the duct and have air ducts travel in a straight line for

improved performance.

Field supplied hardware requires:
• Insulated 12 inch diameter flexible ducts
• Return air grill with 12 inch flange and filter for the room air intake
• Diffuser with 12 inch flange for the cool air outlet
Refer to the maximum static pressure of “Technical Specifications” on

page 58.

CONDENSER
INTAKE

CONDENSER EXHAUST

COOL AIR SUPPLY
(EVAPORATOR)

ROOM AIR
INTAKE

RETURN AIR
GRILL WITH
FILTER REQUIRED

INSULATED
FLEXIBLE DUCT