TROUBLESHOOTING (cont.)

Condition

Checking Area

Possible

Cause

Remedy

Self-

Diagnostic

Codes

(Wall

mounted

controller)

Buzzer

Pattern

Unit

does

not

operate

at all.

LCD

displays

self-

diagnostic

codes.

E06

2

Loose CTS3

thermistor

connection

Check connection.

To reset: Press

RESET button.

Defective CTS3

thermistor

(short or open)

Replace CTS3

thermistor.

To reset: Press

RESET button.

E08

Wall mounted

controller lost

communication

with the unit for

more than 10

seconds.

Check for connection

or interference.

To reset: Press

RESET button.

E09

4

Evaporator fan

motor is locked.

Check for any foreign

object which may

cause fan lock.

To reset: Press

RESET button.

E10

4

Condenser fan

motor is locked.

Check for any foreign

object which may

cause fan lock.

To reset: Press

RESET button.

OL

4

Compressor

overload protection

is activated by

refrigerant leakage.

Repair of the leaking

section and recharge

of the correct amount

of refrigerant are

required. Contact

your MovinCool

reseller or a qualified

technician.

To reset: Press

RESET button.

E11

4

Relay board

communication

error occurs for 40

seconds.

Check all wire

connection on the

relay board.

To reset: Press

RESET button.