Motor does not restart after power loss, And dm-) – Yaskawa Z1000U User Manual

Page 227

Advertising
background image

Cause

Possible Solutions

Hunting occurs at start.

Increase the S-curve time at the start of acceleration (C2-01).

Too much current is flowing through the drive.

For special-purpose motors, enter the correct data to all E5 parameters according to the test report

provided for the motor.

u

Motor Does Not Restart after Power Loss

Cause

Possible Solutions

The Run command was not issued again when power

was restored.

• Check the sequence and wiring that has been set up to enter the Run command.
• A relay should be set up to make sure the Run command remains enabled throughout any power

loss.

The relay that is supposed to maintain the Run

command has been switched off.

Check wiring and circuitry for the relay intended to keep the Run command enabled.

u

The Safety Controller Does Not Recognize Safe Disable Monitor Output Signals
(Terminals DM+ and DM-)

Cause

Possible Solutions

There is faulty wiring in the Safe Disable monitor

output terminals.

• Check the Safe Disable monitor output terminal wiring.
• Correct any wiring mistakes.

5.10 Troubleshooting without Fault Display

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

227

5

Troubleshooting