Output terminals, Serial communication terminals – Yaskawa Z1000U User Manual

Page 83

Advertising
background image

n

Output Terminals

Table 3.8

lists the output terminals on the drive. Text in parenthesis indicates the default setting for each multi-function output.

Table 3.8 Control Circuit Output Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Page

Fault Relay

Output

MA N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

MB

N.C. output

MC

Fault output common

Multi-Function
Digital Output

<1>

MD N.O.

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

282

ME

N.C. Output

MF

Common (Speed agree)

M1

Multi-function digital output (During run)

30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A

Minimum load: 5 Vdc, 10 mA

M2
M3

Multi-function digital output (Zero speed)

M4

Monitor Output

FM

Analog monitor output 1 (Output frequency)

-10 to +10 Vdc, or 0 to +10 Vdc

286

AM Analog monitor output 2 (Output current)

AC

Monitor common

0 V

External Power

Supply

24V External Power Supply

24 V (Max. 150 mA)

<1> Refrain from assigning functions to digital relay outputs that involve frequent switching, as doing so may shorten relay performance life. Switching

life is estimated at 200,000 times (assumes 1 A, resistive load).

n

Serial Communication Terminals

Table 3.9 Control Circuit Terminals: Serial Communications

Type

No.

Signal Name

Function (Signal Level)

Serial Communication

(APOGEE FLN,

BACnet, MEMOBUS/

Modbus, or Metasys
N2)

<1>

R+

Communications input (+)

APOGEE FLN, BACnet, MEMOBUS/

Modbus, or Metasys N2 communication: Use

an RS-422 or RS-485 cable to connect the

drive.

• APOGEE FLN

Comm. RS-422/

RS-485, 4.8 kbps

• BACnet Comm.

RS-485, max. 76.8

kbps

• MEMOBUS/

Modbus Comm.

RS-422/RS-485,

max. 115.2 kbps

• Metasys N2 Comm.

RS-422/RS-485, 9.6

kbps

R-

Communications input (-)

S+

Communications output (+)

S-

Communications output (-)

IG

Communications ground

0 V

FE

Option card ground

<1> Enable the termination resistor in the last drive in an APOGEE FLN, BACnet, MEMOBUS/Modbus, or Metasys N2 network by setting DIP switch

S2 to the ON position.

Refer to Control I/O Connections on page 88

for more information on the termination resistor.

3.9 Control Circuit Wiring

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

83

3

Electrical Installation