Main circuit terminal and motor wiring, Cable length between drive and motor – Yaskawa Z1000U User Manual

Page 76

Advertising
background image

Drive

Model

Terminal

For USA and Canada

For South America

Screw

Size

Tightening

Torque

N·m (lb.in.)

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

Recomm. Gauge

mm

2

(AWG, kcmil)

Wire Range

mm

2

(AWG, kcmil)

4o0216

R/L1, S/L2, T/L3

50 × 2

(1/0 × 2P)

35 to 95 × 2

(2 to 4/0 × 2P)

35 × 2P

(1 × 2P)

25 to 95 × 2P

(3 to 4/0 × 2P)

M10

15 to 20

(133 to 177)

U/T1, V/T2, W/T3

50 × 2

(1/0 × 2P)

35 to 95 × 2

(2 to 4/0 × 2P)

35 × 2P

(1 × 2P)

25 to 95 × 2P

(3 to 4/0 × 2P)

M10

25

(3)

25 to 95

(4 to 4/0)

35

(1)

25 to 95

(3 to 4/0)

M12

31.4 to 39.2

(278 to 347)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1.2 to 2.0

(10.6 to 17.7)

4o0240

R/L1, S/L2, T/L3

50 × 2

(1/0 × 2P)

50 to 95 × 2

(1/0 to 4/0 × 2P)

50 × 2P

(1/0 × 2P)

35 to 95 × 2P

(1 to 4/0 × 2P)

M10

15 to 20

(133 to 177)

U/T1, V/T2, W/T3

50 × 2

(1/0 × 2P)

50 to 95 × 2

(1/0 to 4/0 × 2P)

50 × 2P

(1/0 × 2P)

35 to 95 × 2P

(1 to 4/0 × 2P)

M10

35

(2)

35 to 95

(2 to 4/0)

50

(1/0)

35 to 95

(1 to 4/0)

M12

31.4 to 39.2

(278 to 347)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1.2 to 2.0

(10.6 to 17.7)

4o0302

<1>

R/L1, S/L2, T/L3

70 × 2

(3/0 × 2P)

50 to 95 × 2

(1/0 to 4/0 × 2P)

70 × 2P

(3/0 × 2P)

50 to 95 × 2P

(1/0 to 4/0 × 2P)

M10

15 to 20

(133 to 177)

U/T1, V/T2, W/T3

70 × 2

(3/0 × 2P)

50 to 95 × 2

(1/0 to 4/0 × 2P)

70 × 2P

(3/0 × 2P)

50 to 95 × 2P

(1/0 to 4/0 × 2P)

M10

35

(1)

35 to 150

(1 to 300)

70

(3/0)

35 to 150

(1 to 300)

M12

31.4 to 39.2

(278 to 347)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1.2 to 2.0

(10.6 to 17.7)

4o0361

<1>

R/L1, S/L2, T/L3

95 × 2

(4/0 × 2P)

70 to 95 × 2

(3/0 to 4/0 × 2P)

95 × 2P

(4/0 × 2P)

70 to 95 × 2P

(3/0 to 4/0 × 2P)

M10

15 to 20

(133 to 177)

U/T1, V/T2, W/T3

95 × 2

(4/0 × 2P)

70 to 95 × 2

(3/0 to 4/0 × 2P)

95 × 2P

(4/0 × 2P)

70 to 95 × 2P

(3/0 to 4/0 × 2P)

M10

50

(1/0)

50 to 150

(1/0 to 300)

95

(4/0)

70 to 150

(3/0 to 300)

M12

31.4 to 39.2

(278 to 347)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1.2 to 2.0

(10.6 to 17.7)

4o0414

<1>

R/L1, S/L2, T/L3

150 × 2

(300 × 2P)

95 to 150 × 2

(4/0 to 300 × 2P)

95 × 2P

(4/0 × 2P)

95 to 150 × 2P

(4/0 to 300 × 2P)

M12

25 to 35

(221 to 310)

U/T1, V/T2, W/T3

150 × 2

(300 × 2P)

95 to 150 × 2

(4/0 to 300 × 2P )

95 × 2P

(4/0 × 2P)

95 to 150 × 2P

(4/0 to 300 × 2P )

M12

50

(1/0)

50 to 240

(1/0 to 400)

95

(4/0)

70 to 240

(3/0 to 400)

M12

31.4 to 39.2

(278 to 347)

p1, n1

2.5

(14)

2.5 to 4

(14 to 12)

2.5

(14)

2.5 to 4

(14 to 12)

M4

1.2 to 2.0

(10.6 to 17.7)

<1> Take additional measures in accordance with IEC/EN 61800-5-1 when wiring an EMC filter is installed. Refer to the User Manual for details.

u

Main Circuit Terminal and Motor Wiring

This section outlines the various steps, precautions, and checkpoints for wiring the main circuit terminals and motor terminals.

NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order for the drive and motor should

match. Failure to comply with proper wiring practices may cause the motor to run in reverse if the phase order is backward.

NOTICE: Route motor leads U/T1, V/T2, and W/T3 separate from all other leads to reduce possible interference related issues. Failure to

comply may result in abnormal operation of drive and nearby equipment.

n

Cable Length Between Drive and Motor

Voltage drop along the motor cable may cause reduced motor torque when the wiring between the drive and the motor is too

long, especially at low frequency output. This can also be a problem when motors are connected in parallel with a fairly long

motor cable. Drive output current will increase as the leakage current from the cable increases. An increase in leakage current

may trigger an overcurrent situation and weaken the accuracy of the current detection.

3.8 Main Circuit Wiring

76

YASKAWA ELECTRIC TOEP C710636 10B Z1000U HVAC MATRIX Drive User Manual

Advertising