Intel Entry Redundant Power 2U ERP2U User Manual

Page 12

Advertising
background image

SSI

ERP2U Power Supply Design Guide, V1.0

- 12 -

5.8 AC Line Transient Specification

STATUS

Recommended

AC line transient conditions shall be defined as “sag” and “surge” conditions. Sag conditions (also referred to as
“brownout” conditions) will be defined as the AC line voltage dropping below nominal voltage. Surge conditions
will be defined as the AC line voltage rising above nominal voltage.

The power supply shall meet the requirements under the following AC line sag and surge conditions.

Table 4: AC Line Sag Transient Performance

AC Line Sag

Duration

Sag

Operating AC Voltage

Line Frequency

Performance Criteria

Continuous

10%

Nominal AC Voltage ranges

50/60 Hz

No loss of function or performance

0 to 1 AC
cycle

100%

Nominal AC Voltage ranges

50/60 Hz

No loss of function or performance

>1 AC cycle

>10%

Nominal AC Voltage ranges

50/60 Hz

Loss of function acceptable, self
recoverable

Table 5: AC Line Surge Transient Performance

AC Line Surge

Duration

Surge

Operating AC Voltage

Line Frequency

Performance Criteria

Continuous

10%

Nominal AC Voltages

50/60 Hz

No loss of function or performance

0 to ½ AC
cycle

30%

Mid-point of nominal AC
Voltages

50/60 Hz

No loss of function or performance

5.9 AC Line Fast Transient Specification

STATUS

Recommended

The power supply shall meet the EN61000-4-5 directive and any additional requirements in IEC1000-4-5:1995
and the Level 3 requirements for surge-withstand capability, with the following conditions and exceptions:

These input transients must not cause any out-of-regulation conditions, such as overshoot and
undershoot, nor must it cause any nuisance trips of any of the power supply protection circuits.

The surge-withstand test must not produce damage to the power supply.

The supply must meet surge-withstand test conditions under maximum and minimum DC-output load
conditions.