Ac input requirements – Intel Entry Redundant Power 2U ERP2U User Manual

Page 9

Advertising
background image

SSI

ERP2U Power Supply Design Guide, V1.0

- 9 -

4.2.1

Redundant Cooling

STATUS

Recommended

It is recommended that the power supply cooling be redundant. This means the cooling device is located in the
hot swap power supply modules or there are redundant devices located on the cage.

4.3 Temperature Requirements

STATUS

Recommended

The power supply shall operate within all specified limits over the T

op

temperature range. All airflow shall pass

through the power supply and not over the exterior surfaces of the power supply.

Table 1: Thermal Requirements

ITEM

DESCRIPTION

MIN

MAX

UNITS

T

op

Operating temperature range.

0

50

°

C

T

non-op

Non-operating temperature range.

-40

70

°

C

The power supply must meet UL enclosure requirements for temperature rise limits. All sides of the power supply
with exception to the air exhaust side, must be classified as “Handle, knobs, grips, etc. held for short periods of
time only”.

5

AC Input Requirements

STATUS

Required

The power supply modules shall incorporate universal power input with active power factor correction, which shall
reduce line harmonics in accordance with the EN61000-3-2 and JEIDA MITI standards.

5.1 AC Inlet Connector

STATUS

Required

The AC input connector shall be an IEC 320 C-14 power inlet. This inlet is rated for 15 A/250 VAC. This
connector may be located on the module or on the cage.

5.2 Redundant AC Inlets

STATUS

Recommended

The power supply assembly may have dual redundant AC inlets. The power supply shall be able to operate over
its full, specified range of requirements with either or both AC input powered. If there is a loss of one AC inlet the