Samson 5476 User Manual

Page 104

Advertising
background image

Parameters

Range of values

Return flow limitation temperature
during DHW heating

20 to 90 °C

Heat exchanger inlet temp. limit

20 to 130 °C

Solar circuit pump ON

0 to 30 °C

Solar circuit pump OFF

0 to 30 °C

Solar charging OFF

20 to 90 °C

Station address

1
1

to 247, 8 bit
to 999, 16 bit

Baud rate

150 to 9600

Time schedules for heating circuit and underfloor heating circuit (system Anl 9)

Heating circuit 1

Heating circuit 2 or

underfloor heating circuit (Anl 9)

Start – Stop (1)

Start – Stop (2)

Start – Stop (1)

Start – Stop (2)

Monday (1)

Tuesday (2)

Wednesday (3)

Thursday (4)

Friday (5)

Saturday (6)

Sunday (7)

Public holidays and vacations

Public holidays
Date

Vacations
Start – Stop

104

EB 5476 EN

Appendix