2.5

Calibrating sensors

The connected sensors are calibrated in the configuration level. The following applies:

4

FB16 = ON, select “P1000“:

Pt 1000 and Pt 100 sensors

4

FB16 = ON, select “ntc“:

NTC and Pt 100 sensors

4

FB16 = OFF:

PTC and Pt 100 sensors (default setting)

The resistance values of the sensors can be found on page 98.

If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sensor,
the currently displayed sensor value must be changed such that it matches the temperature (ref-
erence temperature) measured directly at the point of measurement.
Perform the calibration in function block FB33. The function block FB33 always remains
activated.

Proceed as follows:

Switch to the parameter level.
Display: Time,

blinks

Switch to the configuration level.
Display: Current system code number (Anl),

blink

Select function block level 24 to 47.

Select function block FB33.

Activate function block FB33.
Display: 0 0 0 0 0

Enter currently valid key number.
Display: Flow sensor, measured temperature

Flow sensor (VF1)

If necessary, select other sensors that you want to calibrate.

Outdoor sensor (AF)

Room sensor (RF)

Return flow sensor (RüF1)

20

EB 5476 EN

Start-up