FB Function

WE Anl Comments

22 Current input for

flow rate
measurement

OFF All FB22 = ON: Current input active

Select:

0: 0 to 20 mA signal feedforwarding
4: 4 to 20 mA signal feedforwarding

A 50-

W

resistor must be connected to terminals 15 (+) and GND

(terminals ½) in parallel to the current signal
FB22 = OFF: Pulse input active
Setting only possible after entering key number!

23 Flow rate or

capacity limitation

OFF All FB23 = ON and FB22 = OFF: Limitation with pulse input

Function block parameters:
Max. limit value / 3 to 500 pulse/h (500 pulse/h)
Limiting factor / 0.1 to 10 (1)
Max. limit value for DHW / 3 to 500 pulse/h

(500 pulse/h)

Limiting factor / 0,1 to 10 (1)
FB23 = ON and FB22 = ON: Limitation with current input
Function block parameters:
Upper measuring range / 0.01 to 650 m

3

/h (10.00 m

3

/h)

Min. limit value / 0.01 to 650 m

3

/h (0.01 m

3

/h)

Max. limit value / 0.01 to 650 m

3

/h (9 m

3

/h)

Setting only possible after entering key number!

The following function blocks are in the second level

24
(0)

Potentiometer input
1 to 2 k

W

OFF

FB24 = ON: Potentiometer input connected at terminal 12
FB24 = OFF: Type 5244 or 5257-5 Room Panel connected

25
(1)

Release for
control/external
demand over BE1

OFF

1

to

11*

FB25= ON: Configuration of BE1
Select:

FErn: Release for control
bEd: Demand of a minimum flow temperature

Function block parameter:
Min. flow temperature for external demand / 20 to 130 °C (20 °C)
* Not Anl 4, 5 and 9 with solar system or Anl 11 with VF3

26
(2)

Circulation pump
(ZP)

OFF 2 to

11

FB26 = ON: Circulation pump operation acc. to time schedule
FB26 = OFF: ZP operation switches off SLP

27
(3)

Flow sensor VF3

OFF 3, 8,

11

FB27 = ON: Sensor activated

28
(4)

Pump management
UP1

OFF All FB28 = ON: BA9 not active outside times-of-use

FB28 = AUS: BA9 active outside times-of-use

84

EB 5476 EN

Appendix