Appendix, Eb 5476 en – Samson 5476 User Manual

Page 92

Advertising
background image

Display

Parameter designation
Range of values (default values)

System Anl 9, underfloor heating circuit

Gradient, flow

0.2 to 3.2 (0.8)

Level, flow

–30 to 30 °C (–5 °C)

4-point characteristic

Press key to set parameters
outdoor temperature, point 1 to 4
flow temperature, point 1 to 4.

4-point characteristic, outdoor temperature

Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.

–30 to 20 °C
( point 1: –15 °C, point 2: –5 °C, point 3: 5 °C, point 4: 15 °C)

92