Functi on block list 81 – Samson 5476 User Manual

Page 81

Advertising
background image

12

Appendix

12.1 Function block list

FB Function

WE Anl Comments

0 Optimization

OFF

FB0 = ON: Optimization active; when FB0 = ON also FB13 =
ON

1 Adaptation

OFF

FB1 = ON: Adaptation active; when FB1 = ON also FB13 = ON

2 Flash adaptation

OFF

FB2 = ON: Flash adaptation active; when FB2 = ON also
FB13 = ON

3 Summer mode

OFF

FB3 = ON: Summer mode active
Function block parameters

:

Start summer mode / 01.01 to 31.12 (01.06)
End summer mode / 01.01 to 31.12 (30.09)
Outdoor temperature limit / 0 to 30 °C (18 °C)

4 Delayed outdoor

temperature
adaptation

OFF

FB4 = ON: Temperature adaptation active
Ab:

Active when outdoor temperature drops

AufAb: Active when outdoor temperature increases or drops
Function block parameter:
Delay / 0.2 to 6 °C/h (3 °C/h)

5 Automatic summer

time/winter time
changeover

ON

FB5 = ON: Changeover active

6 Public

holidays/vacation
data for DHW

OFF

2

to

11

FB6 = ON: Public holiday and vacation data entered also
applies to DHW heating

7 Thermal

disinfection

OFF 2, 3,

4, 5,
7, 8,
9,11

FB7 = ON: Thermal disinfection active; when FB7 = ON also FB14
= ON
Function block parameter

:

Day of week / 1 to 7 (Mon to Sun), 1–7 (3)

8 Priority for DHW

circuit

OFF 4, 5,

6, 7,

8,

11

FB8 = ON: Priority active
Ab:

Priority through set-back operation

In:

Priority through reverse control

Function block parameter

:

Activate priority in case of deviation / 2 to 10 min (10 min)