5 functions of the hea ting cir cuit 40, 1 weat her-com pen sa ted con trol 40, Cha rac te ris tic 40 – Samson 5476 User Manual

Page 40: Hea ting cha rac te ris tic 40, We at her-com pen sa ted con trol 40, Functions of the heating circuit, Weather-compensated control, 5functions of the heating circuit, 1 weather-compensated control

Advertising
background image

5

Functions of the heating circuit

Which controller functions are available depends on the selected system code number (Anl).

5.1

Weather-compensated control

When weather-compensated control is used, the flow temperature is controlled according to the
outdoor temperature. The heating characteristic in the controller defines the flow temperature
set point as a function of the outdoor temperature (–> Fig. 2). The outdoor temperature required
for weather-compensated control is measured at the outdoor sensor or received over a current
input.

Measured at the outdoor sensor

Function

WE

Configuration

Outdoor temperature – Current input

OFF

FB18 = OFF

Received over (0)4 to 20 mA current input

(a 50

W

resistor must be connect to terminals 7(+)

and GND (terminals ½) parallel to the current signal)

40

EB 5476 EN

Functions of the heating circuit

Fig. 2 · Gradient characteristics

t

VL

Flow temperature

t

A

Outdoor temperature