Parker Hannifin Dynaserv G2 User Manual

Page 163

Advertising
background image

94

Position command differential value excessive error
processing type

Always

Minimum value: 0
Maximum value: 5
Initial value:

1

Unit:

None

Long:

Short:

Over_dScmdErrorType

OVP_ErrTyp

Specify the processing type when a position command differential value excessive error occurs.

When operating the built-in controller axis:

0: Maintains the servo status after the axis operation stops (low level).
1: Turns the servo OFF after the axis operation stops (low level).
2: Stops the axis operation (low level) and turns the servo OFF immediately.
3: Maintains the servo status after the axis operation stops (high level).
4: Turns the servo OFF after the axis operation stops (high level).
5: Stops the axis operation (high level) and turns the servo OFF immediately.

When performing the higher controller follow-up:

0: Switches to the built-in controller, and maintains the servo status after a deceleration stop.
1: Switches to the built-in controller, and turns the servo OFF after a deceleration stop.
2: Switches to the built-in controller, performs a deceleration stop, and turns the servo OFF immediately.
3: Switches to the built-in controller, and maintains the servo status after an immediate stop.
4: Switches to the built-in controller, and turns the servo OFF after an immediate stop.
5: Switches to the built-in controller, performs an immediate stop, and turns the servo OFF immediately.

95

Over-travel error function in the + direction processing
type

Always

Minimum value: 0
Maximum value: 5
Initial value:

1

Unit:

None

Long:

Short:

+Hot_ErrorType

+Hot_ErrTyp

Specify the processing type when an over-travel error in the + direction occurs.

When operating the built-in controller axis:

0: Maintains the servo status after the axis operation stops (low level).
1: Turns the servo OFF after the axis operation stops (low level).
2: Stops the axis operation (low level) and turns the servo OFF immediately.
3: Maintains the servo status after the axis operation stops (high level).
4: Turns the servo OFF after the axis operation stops (high level).
5: Stops the axis operation (high level) and turns the servo OFF immediately.

When performing the higher controller follow-up:

0: Switches to the built-in controller, and maintains the servo status after a deceleration stop.
1: Switches to the built-in controller, and turns the servo OFF after a deceleration stop.
2: Switches to the built-in controller, performs a deceleration stop, and turns the servo OFF immediately.
3: Switches to the built-in controller, and maintains the servo status after an immediate stop.
4: Switches to the built-in controller, and turns the servo OFF after an immediate stop.
5: Switches to the built-in controller, performs an immediate stop, and turns the servo OFF immediately.