Inputs - outputs – Micromod RetroPAK: SLC Configuration Manual User Manual

Page 148

Advertising
background image

Command Series Migration to MOD 30ML

Pre-configured Dual Loop PID with Remote SP

reference that includes listing of most commonly used / changed attribute and inputs and
outputs. Necessary block configuration tabs are also explained to make it easier.

INPUTS - OUTPUTS

Signal Block

Type

Description

S1

PID

Input – S1
Floating Point

Result (R) of the VCI block VCI1 is
already connected to PID.S1 signal of
the compound for the first loop.

Result (R) of the VCI block VCI1 is
already connected to PID.S1 signal of
the compound for the second loop.

Process Input signals.

S1Q

QUALLOGIC

Output – S1Q
Boolean (Discrete)

Connect to the QUALLOGIC.S1Q
signal of the compound. Process Input
Quality

S2

PID

Input – S2
Floating Point

Result (R) of the VCI block VCI2 is
already connected to PID.S2 signal of
the compound for the first loop.

Result (R) of the VCI block VCI2 is
already connected to PID.S2 signal of
the compound for the second loop.

Remote Setpoint signal.

S3

PID

Input – S3
Floating Point

Connect to the PID.S3 signal of the
compound. Track Reference.

S4

PID

Input – S4
Boolean

Connect to the PID.S4 signal of the
compound. Track Switch.

S5

PID

Input – Floating
Point

Change in the Control tab of the
corresponding PID block. Change the
value for MANUAL RESET – BASE
VALUE.

S6

PID

Input – S6
Floating Point

Feed-forward input for the PID. Enable
in the Options tab of the PID block.
Change the calculation type to Add.
Connect the feed forward input to the
PID.S6 signal of the compound.

S7 N/A

N/A

N/A

S8 N/A

N/A

N/A

S9 N/A

N/A

N/A

P4- 2