Changing engineering ranges and alarm trip values – Micromod RetroPAK: SLC Configuration Manual User Manual

Page 68

Advertising
background image

Command Series Migration to MOD 30ML

Function Codes – Gallery Tutorial

CHANGING ENGINEERING RANGES AND ALARM TRIP VALUES

18. The FC156 PID (PV/LOCAL SP) has default values for the process variable range (0

to100). We need to change this to 0 – 200 to match the input range defined in step 14.

• Open the compound by first selecting it and then by clicking on the right mouse button. A

context sensitive menu will appear as shown in the next figure:

Figure 2 .42.

Open Compound

• Click on the Open Compound item from this menu. This will open the compound and

display the function blocks inside. See the next figure:

Figure 2 .43.

Inside the FC 150
PID (PV/LOCAL
SP) Compound

• Select the function block ENG (Expression block). This function block is where you

would set the engineering ranges, alarm setpoints and initial PID settings. Double-click on
it to open it.

2 - 30