Command Series Migration to MOD 30ML

Extras – Reject to Manual

INPUTS - OUTPUTS

Signal

Type

Block

Description

S1

Input – S1
Discrete

QUALLOGIC
(EX)

Connect to the QUALLOGIC.S1 signal
of the compound. Averaged Value.

S2

Input – S2
Short State

TRIGGER
(SM)

Connect to the TRIGGER.S2 signal of
the compound.

APPLICATIONS

This compound can be used for an on demand write (on a low to high transition of the S2
input) for any attribute of a function block. This is useful especially if the attribute is not
connectable (for example OPMS, SP of the PID block). The data to be written can be
specified in the SM block’s configuration I the Data Source field as shown in the figure
below or can be connected to the DATAINP attribute of the SM block.

Figure R .2.

Reject to Manual
SM block

R - 2