Command Series Migration to MOD 30ML

Function Code 3 - Lead / Lag

Lag Function

:

To select the lag function, leave S3 at its initial value (0) and enter a number for S4. The
equation then becomes:

Y = YL +

S3 * ( S1 - S1L)

S4 + DT

Y = YL +

S3 * ( S1 - S1L)

S4 + DT

Lead Function

:

To select only a lead function, leave S4 at its initial value of zero and enter a number for
S3. The equation then becomes:

Y = YL +

[S3 * ( S1 - S1L)] + [DT * (S1 - YL)]

DT

Y = YL +

[S3 * ( S1 - S1L)] + [DT * (S1 - YL)]

DT

APPLICATIONS

The next figure is a simplified example of using function code 3 in boiler applications.
This

shows function code 3 used as a lag to delay decreases in airflow for a load decrease.

Figure 3 .2.

Lead Function
example

The next figure shows function code 3 used as a lead/lag to compensate for drum level
shrink and swell due to changes in steam flow.

Figure 3 .3.

Lead/Lag Function
Example