LumaStream Trinity Power Cord User Manual

Page 7

Advertising
background image

Document: 66APPMAN-PC Rev: C

22 of 28

11.3 Analog Interface Specifications

The TRINITY PC ANALOG is compatible with commercial dimming panels
and wall box dimmer products meeting IEC 60929 requirements.

The TRINITY PC ANALOG has been tested with the following 0-10 Vdc
Analog wall box dimmer products:

·

HUNT PS LED series

·

LEVITON DECORA IP710_DL

Additional Analog 0-10 Vdc dimmer products may also be compatible with
the TRINITY PC ANALOG. Consult LumaStream for compatibility


11.4 Analog Interface Cabling and Connections

In the end use application, proper separation between the class 2 control
wiring from the analog 0-10 Vdc interface and AC mains must be
observed in accordance with the applicable safety standards and/or
NEC/CEC requirements.

The total run length of the 0-10Vdc control wiring (purple and grey) #18
AWG should not exceed 500 feet (150 meters). In situations where the
control wiring is greater than 500 feet or electrical noise is present,
shielded twisted pair cabling should be used.

Document: 66APPMAN-PC Rev: C

7 of 28

Table 9

Analog Interface Specifications

Control Method

Analog 0-10Vdc
IEC 60929 or
ESTA E1.3-2001
Class 2 outputs

Master, Zone1 Zone2, Zone3, Zone4
outputs each source 0.5mA
maximum

Loss of Analog
Input Signal

Outputs will go to 100% light intensity in less than 1 second

Connection Method

UL recognized cage clamp connector
12 AWG to 28 AWG wiring

Electrical Isolation

Master, Zone 1, Zone 2, Zone 3, Zone 4 outputs
electrically isolated from earth ground

Table 10

TRINITY Power Cord Multi-Zone Analog Model Options

Model #

# of

Channels

Drive

Current

Output Voltage

Range (under

load Condi-

tions)

Maximum #
of LEDs per

Channel

(typical)

70-12-0350-12Z-PC

12

350 mA

12 to 47 Vdc

4 to 12

70-09-0500-12Z-PC

9

500 mA

12 to 47 Vdc

4 to 12

66-12-0700-12Z-PC

12

700 mA

6 to 27 Vdc

2 to 8

66-09-1000-12Z-PC

9

1000mA

6 to 27 Vdc

2 to 8

Table 11

Multi-Zone Analog Interface Specifications

Control Method

Analog 0-10Vdc
IEC 60929 Annex E Out-
puts 0.5mA maximum
Or
Variable 0-10Vdc Voltage
Source

Class 2 outputs

Master Control:
Simultaneous control of all
output channels

Zonal Control:
Independent control of up to 12 channels

Loss of Analog
Input Signal

Outputs will go to 100% light intensity in less than 1 second

Connection Method

UL recognized cage clamp connector
14 AWG to 28 AWG wiring

Electrical Isolation

Master, Zone 1 to Zone 12 outputs
electrically isolated from earth ground

Advertising