CT-6500 Series 2 Operating Instructions

31

Table 5.0 Close-Open Operation Using Contact Channel #1

STEP OPERATION

ACTION DISPLAY

1

READY TIMER FOR BREAKER OPERATION.

PRESS #1 KEY.

INSERTION RESISTOR?

1.NO

2.YES

2

SELECT NO INSERTION RESISTOR.

PRESS #1 KEY.

TIMING WINDOWS:

1.WINDOW = 1 SEC

2.WINDOW = 10 SEC

3.WINDOW = 20 SEC

3

SELECT 1-SECOND WINDOW.

PRESS #1 KEY.

TRIGGER MODE:

1.INTERNAL TRIGGER

2.EXTERNAL TRIGGER

4

SELECT INTERNAL TRIGGER.

PRESS #1 KEY.

TIMING MODE:

1. OPEN

2. CLOSE

3.

O-C

4.

C-O

5. O-C-O

5

SELECT CLOSE-OPEN OPERATION.

PRESS #4 KEY.

C-O Second Trigger:

1. Contact #1 CLOSE

2. Set DELAY

3. No DELAY

6

SELECT CONTACT #1 CLOSE.

PRESS #1 KEY.

CLOSE-OPEN TIMING

Hold "ARM" Switch

Then "START"

"STOP" to ABORT

7

INITIATE OPEN COMMAND.

HOLD THE "ARM"

SWITCH AND

PRESS THE "START"

KEY.

TEST IN PROGRESS

Hold "ARM" Until

Test complete.

(Up to 25 seconds)

8

ANALYZER IS READY TO OUTPUT RESULTS.

NONE.

1.RUN TEST 06/12/07

2.GET RSLT 19:20:01

3.SET-UP

4.DIAGNOSTIC

NOTE

1. Users can program a delay from 10 to 500 ms between the CLOSE and
OPEN commands. When a delay is used in the operation, it may not
represent a true breaker operating condition.

2. Users can also program in no delay for the operation in which case, the
CLOSE and OPEN commands are initiated at the same time by the CT-
6500.