CT-6500 Series 2 Operating Instructions

66

9.22 Contact Filter Setting

The contact filter setting is applicable for timing shots with insertion resistors only. The
CT-6500 automatically detects the contact time using its own algorithm. However, manual
setting for contact time calculation is made available to the user.
The filter setting of 1 allows the CT-6500 to pick up the first contact transition time after the
resistor contact activity is detected. The filter setting of 300 allows the CT-6500 to pick up the
last contact transition time after the resistor contact activity is detected. Use the steps below to
set contact filtering.

Table 27.0 Set Contact Filter

STEP OPERATION

ACTION

DISPLAY

1

SELECT DIAGNOSTIC.

PRESS # 4 KEY.

1. SLOW-CLOSE TEST

2. CHECK HOOKUP

3. TEST TRANSDUCER

4. NEXT PAGE

2

SELECT NEXT PAGE.

PRESS # 4 KEY.

1. PRINT DATA

2. ENCODER FILTER

3. CONTACT FILTER

3

SELCT CONTACT FILTER.

PRESS # 3 KEY.

ENTER FILTER SETTING

(1 – 300)

CURRENT SETTING: 1

NEW SETTING?

4

ENTER NEW FILTER SETTING.

SELECT 5 SAMPLES.

PRESSS KEY # 5

ENTER FILTER SETTING

(1 – 300)

CURRENT SETTING: 1

NEW SETTING? 5

5

SELECT FILTER SETTING

PRESS “ENTER” KEY.

1.RUN TEST 06/10/07

2.GET RESULTS 20:10:01

3.SETUP

4.DIAGNOSTIC

Note

The CT-6500 will return to automatic filter setting after power is cycled.