9.13 Slow-Close Test

The CT-6500 offers a unique feature called a "Slow-Close" test. The test permits users to

measure the distance a breaker's contact travels from the fully opened position to the point of
contact or "touch" position, and the contact wipe or penetration distance. The test requires the
operator to manually jack the breaker's contact from the fully open position to the fully closed
position.

Contact channel 1, 2, 3 and transducer channel 1 will be used for “Slow-Close” testing. The

CT-6500 will measure the contact touch and contact wipe for each contact channel.

Contact touch is the distance measured from the contact fully open to the first position where

the contact channel is electrically closed.
Contact wipe, or penetration, is the distance measured from the contact’s first, electrically
closed position to the final closed, latching position.

Table 18.0 Performing a Slow-Close Test

STEP OPERATION

ACTION

DISPLAY

1

SELECT DIAGNOSTIC MENU.

PRESS # 4 KEY.

1. SLOW CLOSE TEST

2. CHECK HOOKUP

3. TEST TRANSDUCER

4. NEXT PAGE

2

SELECT SLOW CLOSE TEST.

PRESS # 1 KEY.

BREAKER SLOW CLOSE TEST

RMV CB GND (1 SIDE)

"ENTER" TO BEGIN

3

START SLOW CLOSE TEST.

PRESS THE "ENTER"

KEY.

CONTACT 1:OPEN

CONTACT 2:OPEN

CONTACT 3:OPEN

LIFT TO CLS BREAKER NOW

4

CONTINUE TO CLOSE BREAKER.

NO ACTION.

LIFT BRKR TO CLS POS

THEN PRESS "ENTER"

TO FIND CONTACT WIPE

5

RETURN TO MAIN MENU.

NO ACTION.

1.RUN TEST 06/10/07

2.GET RESULTS 20:10:01

3.SETUP

4.DIAGNOSTIC


NOTE

The user can also save a Slow-Close test report in the EEPROM. A typical report of
a Slow-Close test is shown on in Figure 18.0.