CT-6500 Series 2 Operating Instructions

32

9.1.4 Timing OPEN-CLOSE-OPEN Operation
The OPEN-CLOSE-OPEN operation requires the user to enter two time-delays
between the circuit breaker operations. The time delays are in millisecond intervals.
The first delay is from the first OPEN command to the CLOSE command. The second
delay is from the CLOSE command to the second OPEN command. Refer to Table 6.0
for setting up the OPEN-CLOSE-OPEN operation.

Table 6.0 Open-Close-Open Operation Using Delay

STEP OPERATION

ACTION DISPLAY

1

READY TIMER FOR BREAKER OPERATION.

PRESS #1 KEY.

INSERTION RESISTOR?

1.NO

2.YES

2

SELECT NO INSERTION RESISTOR.

PRESS #1 KEY.

TIMING WINDOWS:

1.WINDOW = 1 SEC

2.WINDOW = 10 SEC

3.WINDOW = 20 SEC

3

SELECT 1-SECOND WINDOW.

PRESS #1 KEY.

TRIGGER MODE:

1.INTERNAL TRIGGER

2.EXTERNAL TRIGGER

4

SELECT INTERNAL TRIGGER.

PRESS #1 KEY.

TIMING MODE:

1. OPEN

2. CLOSE

3.

O-C

4.

C-O

5. O-C-O

5

SELECT OPEN-CLOSE-OPEN OPERATION.

PRESS #5 KEY.

O-C Delay in mS:

(10 – 350)

mSec

ENTER when done

6

SELECT DELAY BETWEEN OPEN-CLOSE

OPERATION.

ENTER DELAY USING

0-9 KEYS, PRESS THE

“ENTER” KEY TO

CONFIRM.

C-O Delay in mS:

(10 – 350)

mSec

ENTER when done

7

SELECT DELAY BETWEEN CLOSE-OPEN

OPERATION.

ENTER DELAY USING

0-9 KEYS, PRESS THE

“ENTER” KEY TO

CONFIRM.

OPEN-CLOSE-OPEN TIMING

Hold "ARM" Switch,

Then "START".

"STOP" to ABORT

8

INITIATE O-C-O COMMAND.

HOLD THE "ARM"

SWITCH AND

PRESS THE "START"

KEY.

TEST IN PROGRESS

Hold "ARM" Until

Test complete.

(Up to 25 seconds)

9

ANALYZER IS READY TO OUTPUT RESULTS.

NONE.

1.RUN TEST 06/12/07

2.GET RSLT 19:20:01

3.SET-UP

4.DIAGNOSTIC