E 5-19, E 5-20, Figure 5-19 – Innotech Genesis II Digital Controller (v5) User Manual

Page 122: Alues shown in, Mpi with isolated rs485, Mpi with non-isolated rs485

Advertising
background image

Genesis II Installation Instructions

Page 122

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

V

AC

V

DC

3.5

Isolated or Non-Isolated

Genesis II Digital Controller

V

AC

V

DC

3.5

V

AC

V

DC

3.5

Results of this test should be

as low as possible to ensure

error free communications

SEE NOTES

1 and 2

Measure AC and DC voltages:

Should be less than 3.5Vac and

between +10Vdc and -5Vdc.

1.

Measure voltages to the Screen

connectors.

2.

NOTES

91 92 93 94

90

+

C

+

-

-

Global

Net

RS-485

1 2 3

20 21

24V 0 Earth

Screen

Measure all voltages to the metal shell of a DB connector on the MPI with the MPI

connected to a PC or Printer which is plugged into a standard power point (outlet).

MODEM

PC

PRINTER

V

AC

V

DC

3.5

MPI With Non-Isolated RS485

MODEM

PC

PRINTER

V

AC

V

DC

24V

MPI With Isolated RS485

Measure AC and DC

voltages: Should be

less than 3.5Vac and

between +10Vdc and

-5Vdc.

Measure AC and DC

voltages: Should be

less than 24Vac and

between +33Vdc and

-33Vdc.

Figure 5-19:  Voltage Check, Isolated/Non-Isolated Digital Controller

Figure 5-20:  Voltage Check, GENII MPI with Isolated/Non-Isolated RS485