Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 4 – Commissioning

4-1.4.2 End of Cable Jumpers

Although the locations of End-of-Cable jumpers are not shown on the computer-generated wiring

diagram, they are easily located close to the unit’s RS485 Comms connector. Figure 4-7 shows the

location of the End-of-Cable jumper for a GENII AI REM unit. Jumpers for other units are similarly

placed. The rule for installing an End-of-Cable jumper is:

• If only one cable is connected into an RS485 Comms connector, a jumper must be installed in that

unit.

• If two cables are connected to the same RS485 Comms connector, the jumper plug must be left

open.

All units along the RS485 Comms network should be carefully checked to ensure that jumpers are

installed only in the last unit in the network.

R

GEN II AI REM

1 2 3

RS485 COMMS

CONNECTIONS

END-OF-CABLE

JUMPER

Figure 4-7:  End of Jumper, Typical Location