Innotech Genesis II Digital Controller (v5) User Manual

Page 44

Advertising
background image

Genesis II Installation Instructions

Page 44

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

3-3.2.1 Power Input

The MPCII Mid Points Controller's power requirements are one of the following:

• 24VAC ±10%, 50/60Hz, Power Consumption: 7 VA

• 24VDC ±10%, Power Consumption: 4 Watts

The operating voltage must meet the requirements of Safety Extra Low Voltage (SELV) to EN60730.

The transformer used must be a safety transformer in compliance with EN60742 and be designed for

100% duty. It must also be sized and fused in compliance with local safety regulations.

A single transformer may be used to supply voltage to more than one unit (such as a MPCII Mid Points

Controller and associated Remote Expansion Modules) providing the planned load is well within the

transformer’s rating. The transformer output terminal designated as AC Neutral must be solidly

earthed to the enclosure’s main earth link.

Power input terminals are Terminals 1, 2 and 3 and are detailed below in Table 3-8:

Terminal

AC Supply

DC Supply

1

24VAC

+24VDC

2

0VAC (Neutral)

-24VDC

3

Earth

Earth

Table 3-8: 

MPCII Mid Points Controller Power Input Signal Conditions

Resistance between Terminal 2 and Earth must be 3

or less.

NOTE

Advertising