4.6 genii do rem relay output module, Genii do rem relay output module, Genii do rem relay output signal conditions – Innotech Genesis II Digital Controller (v5) User Manual

Page 56: E 3-10

Advertising
background image

Genesis II Installation Instructions

Page 56

© Mass Electronics Pty Ltd 2010

Edition 2.0 dated 06/12/2013

The RS485 Comms connection block is in the upper right section of the module and the End of Cable

Jumper is next to it.

Digital Output terminals are located at the bottom of the module; input signal connections are listed

in Table 3-16.

3-4.6 GENII DO REM Relay Output Module

The GENII DO REM Relay Output Module (Figure 3-10) is powered by 24VAC ±10% @ 50/60 Hz. Power

Consumption is 4VA maximum.

The GENII DO REM provides 5 Relay Outputs (2A @ 24VAC – Normally open contacts) to control or

switch field equipment.

R

GENESI S

DIGI TA L OUTPUT

Remote Expansion Modul

e

1 2 3

A B C D E F G H I J

RS485 COMMS

CONNECTIONS

END OF

CABLE

JUMPER

POWER

DIGITAL

OUTPUT

CONNECTIONS

DI1

+

DI2

+

DI3

+

DI4

+

DI5

+

DI6

+

DI7

+

DI8

+

COM

-

COM

-

Figure 3-10:  GENII DO REM Relay Output Module

Normally Open (NO)

Common (COM)

Terminal

Signal

Terminal

Signal

A

NO Relay 1

B

COM Relay 1

C

NO Relay 2

D

COM Relay 2

E

NO Relay 3

F

COM Relay 3

G

NO Relay 4

H

COM Relay 4

I

NO Relay 5

J

COM Relay 5

Table 3-16: 

GENII DO REM Relay Output Signal Conditions