4.2 rem comms connections, Rs485 comms cable connections – Innotech Genesis II Digital Controller (v5) User Manual

Page 51

Advertising
background image

Page 51

Genesis II Installation Instructions

© Mass Electronics Pty Ltd 2010

Chapter 3 – Electrical Installation

3-4.2 REM Comms Connections

The RS485 Comms link between the Genesis II Direct Digital Controller and REMs, or the MPCII Mid

Points Controller and REMs, is designed to allow reliable communications over long distances in

electrically adverse signal conditions.

The following guidelines, which are common to all REMs, should be followed when installing the

RS485 Comms network:

• Cables used for RS485 Comms must be shielded, single twisted pair, 120 Ohms characteristic

impedance with 36 to 45 picoFarads per metre capacitance between conductors.

• The RS485 Comms cable must be organised as a bus topology. See

5-3.3

for a description of bus

topology. To connect a module to the RS485 cable, the cable is cut at the point the module is

to be connected. Then, the two new cable ends are wired into the module. The two shields are

then terminated at terminals marked SHLD1 and SHLD2 respectively. “Stub” connections are not

allowed in the bus topology configuration.

• The cable run between the digital controller and any other REM must not exceed 600 metres in

length.

On most units, the RS485 Comms connection block contains four terminals. The four terminals on

the standard RS485 connection block are:

• S1

Screen of Cable Number 1

+

Positive Comms Line

• -

Negative Comms Line

• S2

Screen of Cable Number 2

The four-terminal arrangement accommodates the use of one or two RS485 Comms cables. A

single cable connection is used when the module is located at the end of the network and two cable

connections are used when the REM is connected to a point in the cable network other than the end.

An End of Cable Jumper plug near the RS485 connection block provides the proper termination

impedance for the Comms line. If only single RS485 Comms cable is connected to the module, the

End of Cable Jumper must be installed. If two cables are fitted, the End of Cable Jumper must be

removed.

The RS485 Comms System will not function properly if the connection polarities are incorrect. Ensure correct

polarity of the connections throughout the length of the Comms Cable.

IMPORTANT

Figure 3-6 shows how to connect a two-cable Comms network to a module. If the module has only

one RS485 Comms cable connected to it, the cable screen must be connected to S1. If two Comms

cables are fitted, the screen of the second cable must be connected to the S2 terminal. Screens must

not be connected to each other.

CABLE #1

CABLE #2

S1

S2

+ _

Figure 3-6:  RS485 Comms Cable Connections

Advertising