44

Chapter 8: Troubleshooting

Product Service 1-800-522-7658, International 816-333-8811


PROBLEM

CAUSE

CORRECTIVE ACTION

(Cont’d.) Remote
blower has excessive
vibration.

Inspect wheel for
damage.

Replace damaged wheel.

Check for objects in
blower wheel.

Remove objects in blower wheel.

Improper inlet
connection.

Review Chapter 3: Getting
Started
. The blower inlet should
be installed with a vibration
damper or flexible duct
connection.

Fume hood has
improper face velocity
.

Blower not sized
properly.

Review Chapter 7: Modifying
Your Blower
. Blower Sizing Size
the blower properly with
equivalent resistance method.

Blower requires
RPM adjustment.

Review Chapter 3: Getting Started
Adjust the fan speed and confirm
blower performance.

Advertising
This manual is related to the following products:

Coated Steel, Fiberglass and PVC Blowers 7183100, Coated Steel, Fiberglass and PVC Blowers 7183000, Coated Steel, Fiberglass and PVC Blowers 7182300, Coated Steel, Fiberglass and PVC Blowers 7182200, Coated Steel, Fiberglass and PVC Blowers 7182100, Coated Steel, Fiberglass and PVC Blowers 7182000, Coated Steel, Fiberglass and PVC Blowers 7181700, Coated Steel, Fiberglass and PVC Blowers 7181600, Coated Steel, Fiberglass and PVC Blowers 7181500, Coated Steel, Fiberglass and PVC Blowers 7181400, Coated Steel, Fiberglass and PVC Blowers 7181300, Coated Steel, Fiberglass and PVC Blowers 7181200, Coated Steel, Fiberglass and PVC Blowers 7181100, Coated Steel, Fiberglass and PVC Blowers 7181000, Coated Steel, Fiberglass and PVC Blowers 7180900, Coated Steel, Fiberglass and PVC Blowers 7180800, Coated Steel, Fiberglass and PVC Blowers 7180700, Coated Steel, Fiberglass and PVC Blowers 7180600, Coated Steel, Fiberglass and PVC Blowers 7180500, Coated Steel, Fiberglass and PVC Blowers 7180400, Coated Steel, Fiberglass and PVC Blowers 7180300, Coated Steel, Fiberglass and PVC Blowers 7180200, Coated Steel, Fiberglass and PVC Blowers 7180100, Coated Steel, Fiberglass and PVC Blowers 7180000, Coated Steel, Fiberglass and PVC Blowers 7071900, Coated Steel, Fiberglass and PVC Blowers 7069700, Coated Steel, Fiberglass and PVC Blowers 7069600, Coated Steel, Fiberglass and PVC Blowers 7069500, Coated Steel, Fiberglass and PVC Blowers 7069400, Coated Steel, Fiberglass and PVC Blowers 7069300, Coated Steel, Fiberglass and PVC Blowers 7069200, Coated Steel, Fiberglass and PVC Blowers 7069100, Coated Steel, Fiberglass and PVC Blowers 7069000, Coated Steel, Fiberglass and PVC Blowers 7068900, Coated Steel, Fiberglass and PVC Blowers 7068800, Coated Steel, Fiberglass and PVC Blowers 7068700, Coated Steel, Fiberglass and PVC Blowers 7068600, Coated Steel, Fiberglass and PVC Blowers 7068500, Coated Steel, Fiberglass and PVC Blowers 7068400, Coated Steel, Fiberglass and PVC Blowers 7068300, Coated Steel, Fiberglass and PVC Blowers 7068200, Coated Steel, Fiberglass and PVC Blowers 7068100, Coated Steel, Fiberglass and PVC Blowers 7068000