C. interface connections, Tables, 1 interface connections – Emerson MicroCEM User Manual

Page 47: 2 ac power connection terminal assignments, 3 analog output terminal assignments, C. interface connections -11, Table 2-1, Interface connections -11, Table 2-2, Ac power connection terminal assignments -11

Advertising
background image

Instruction Manual

748467-A

January 2002

Rosemount Analytical Inc. A Division of Emerson Process Management

Installation 2-11

Model MicroCEM

c. Interface Connections

Connection

Designator

Shell

Size

No.

Contacts

AWG

Table

AC Power

J1

12

3

16

Table 2-2

Analog Interface

J2

12

22

26, 24, 22

Table 2-3

Digital Interface

J3

14

37

26, 24, 22

Table 2-4

RS232

J4

10

13

28, 26, 24

Table 2-5

LAN Interface

J5

8

6

28, 26, 24, 22

Table 2-7

RS485

J6

8

3

24, 22, 20

Table 2-6

Phone Line (Modem)

J7

8

3

24, 22, 20

Table 2-8

Antenna (Peltier Power)

J8

16

3

14, 12

Table 2-9

Table 2-1. Interface Connections

SIGNAL NAME

DEFINITION

PIN

L1

A

L2

85-264 VAC, 47-440 Hz

C

GND

AC Ground

B

Table 2-2. AC Power Connection Terminal Assignments

SIGNAL NAME

DEFINITION

PIN

O

2

CL+

1

O

2

CL-

O

2

Reading, 4-20 mA Output

2

COCL+

3

COCL-

CO Reading, 4-20 mA Output

4

NO

X

+

5

NO

X

-

NO

X

Reading, 4-20 mA Output

6

EXP1CL+

7

EXP1CL-

External process No. 1, Current Loop input, 4-20 mA

8

EXP2CL+

9

EXP2CL-

External process No. 2, Current Loop input, 4-20 mA

10

BAROP+

11

BAROP-

Barometric pressure Compensator 0-10V input

12

Table 2-3.

Analog Output Terminal Assignments

Advertising