F. alarm log file format, 9 alarm log file format, Alarm log file format -20 – Emerson MicroCEM User Manual

Page 72: Table 3-9, Model microcem

Advertising
background image

Instruction Manual

748467-A
January 2002

3-20 Operation

Rosemount Analytical Inc. A Division of Emerson Process Management

Model MicroCEM

f.

Alarm Log File Format

The log file contains data in a flat, AS-
CII, CSV file. The following are the
fields of the file, in order of occurrence.

The days or months maintained in the
Alarm Log depends on how often trou-
ble conditions are recorded. If there
are rarely alarm conditions recorded,
there is enough space for many years
of alarm logs to be recorded.

Name

Description

Example

Date/Time

Month-day-year Hours:Minutes:Seconds

3-7-2001 10:24:57

Fault Level

1=informational, 2=warning, 3=critical

3

Fault Type

0 = O2 Calibration Failed

1 = CO Calibration Failed **

2 = NOx Calibration Failed

3 = O2 High Limit

4 = O2 Low Limit

5 = CO High Limit **

6 = CO Low Limit **

7 = NOx High Limit

8 = NOx Low Limit

9 = O2 Emission Limit

10 = CO Emission Limit **

11 = NOx Emission Limit

12 = 5 Volt Fault **

13 = 6 Volt Fault **

14 = 24V Over Max

15 = 24 Low Min

16 = Converter Over Temp

17 = Converter Low Temp

18 = Converter On Failed **

19 = Converter Off Failed **

20 = Zone Over Temp

21 = Zone Low Temp

22 = Zone Heater On Failed **

23 = Zone Heater Off Failed **

24 = Zone Cooler On Failed **

25 = Zone Cooler Off Failed **

26 = Heater Fan On Failed **

27 = Heater Fan Off Failed **

28 = Cooler Fan On Failed **

29 = Cooler Fan Off Failed **

30 = PDT Over Temp

31 = PDT Low Temp

32 = PDT On Failed **

33 = PDT Off Failed **

34 = PMT Over Temp

35 = PMT Low Temp

36 = PMT On Failed **

37 = PMT Off Failed **

38 = O2 Over Temp **

39 = O2 Low Temp **

40 = O2 On Failed **

41 = O2 Off Failed **

42 = Warmup Time Limit

70 = IO Board Failed

2

Fault Description

ASCII string describing fault. Up to 200 characters.

CO Calibration Failed

** - Alarm is not implemented in this version of software or reserved for future use.

Table 3-9. Alarm Log File Format

Advertising