Installation Guide

Raven 3104 Pro Category Cabling Guidelines

The USB 3-2-1 Raven 3104 Pro requires a minimum grade of Category 6a cabling to be used in order to reach

100m (328 ft) of extension distance.

The total distance of 100m also includes the length of the patch cable should one be required. Up

to 10m of patch cable can be used, although the remaining 90m distance must consist of solid core

premise cabling.

Furthermore, depending upon specific application requirements, it is recommended that installers keep

in mind how they intend to pull/route the link cable and whether to use Shielded or Foiled cable where

appropriate.

When installing this product, it is appropriate to use Unshielded (UTP) cabling if the cable run installation

meets the following requirements:

The cable is

not

bundled with other cables

The cable is

run

loosely

with other Category cables

The cable is

not

placed close to sources of interference such as power lines and radios

The cable is

not

looped or coiled

When installing this product, Foiled (FTP) or Shielded (STP) cabling must be used if the cable run installation

requires the following cable run installation:

The cable is bundled with other cables

The cable is run tight against other Category cables

The cable is placed near sources of interference like power lines and radios

The cable is looped or coiled

For best performance install the Raven 3104 Pro using Shielded or Foiled CAT 6a/7 cable.

Requirements for Installing the USB 3-2-1 Raven 3104 Pro System

To complete the installation, you will also require the following items that are not included with this system:

USB compatible computer (host computer) with a USB compliant operating system

USB compatible device(s)

CAT 6a/7 Unshielded Twisted Pair (UTP) cable with two RJ45 connectors (if using surface cabling), or

CAT 6a/7 cabling with two information outlets and two CAT 6a/7 patch cords with RJ45 connectors

(if using premise cabling), ensuring the total cable length does not exceed 100m.

6

note

note