Franklin Fueling Systems TS-LLD Installation Manual User Manual

Page 31

Advertising
background image

LSU

Installation

Page

2.2
-

13

2.2

Figure 2.2-14 INCON TS-LLD Installation at External Leak Detector Port

Tank - Pump # 1

("Standard" Single Phase

Installation)

Existing

Conduit

(Pump 1)

TS-LLD CUs

(Control Units):

# 2 and # 1

INCON TS-LLD Line Leak Detector

External Leak Detector Port Installation

Existing

Conduit

(Pump 2)

Submerged

Turbine

Pump (STP)

1

Pump

Relay

Boxes

2

Electrical

Power Panel

Epoxy

Filled

EYS

Seal

Fitting

Tank - Pump # 2

Installation within an

External Leak Detector Port

( not pump housing)

Explosion-

proof

Junction

Boxes

TS-LLD LSU (#2)

(Leak Sensing Unit)

at External Leak Detector Port

TS-LLD LSU (#1)

(Leak Sensing Unit)

at STP housing

Standard

Single Phase Installation

Dispenser

# A

Dispenser

# X

NOTE:

A TS-TGI Tank Gauge Interface

module is required to connect the

TS-LLD Line Leak Detector system

to an INCON TS-1000 Tank Senti-

nel console. See the TS-TGI Install

Manual.

For TS-1001/2001 Tank Sentinel

consoles, use the LLD / I interface

...see the OPTIONAL TS-LLD TANK

SENTINEL ATG CONSOLE

INTERFACE chapter in this manual.

Reference Schematic

Figure 2.3 - 8

Advertising