14.

Appendix

246

Code

Message

Description

11A No effective axis

This error indicates that “axis number assignment” was attempted when no

axis was connected. Or, the axis number of controller may not have been

recognized.

Causes : [1] The controller is not operating properly.

[2] The signal wire (SGA/SGB), and only the signal wire, is broken

in the supplied cable.

[3] If a SIO converter is used, the link cable is not connected

although 24 V is supplied to the converter.

[4] If multiple controllers are linked, two ADRS switches are setting

the same number by mistake.

Actions : [1] Check if the RDY lamp on the controller is lit. If not, the controller

is faulty.

[2] If a spare connection cable is available, try swapping the cable to

see if the problem is resolved.

[3] Eliminate duplicate ADRS switch settings. If the problem still

persists, contact IAI.

122 Input data error

This error indicates that inappropriate data was entered. Check the entered

data.

123 Inconsistent data version This indicates that an attempt was made to send data which was saved on a

controller of an incompatible version.

Check the version of the source controller and that of the destination

controller.

124 Data editing prohibited in

non-MANU teaching mode

This error indicates that an attempt was made to write position data or

parameters to the controller in the AUTO mode or any MANU monitor mode.

The following causes are considered:

‚

The controller’s mode switch is set to “AUTO” (if the controller has a

mode switch).

‚

The PC software is in “MANU monitor mode 1” or MANU monitor mode

2.”

125 Axis operation prohibited in

non-MANU teaching mode

This error indicates that an attempt was made to perform axis operation

(jogging, home return of an operation-prohibited axis, continuous move, etc.)

in the AUTO mode or any MANU monitor mode.

The following causes are considered:

‚

The controller’s mode switch is set to “AUTO” (if the controller has a

mode switch).

‚

The PC software is in “MANU monitor mode 1” or “MANU monitor mode

2.”

20C Start signal ON

This error indicates that the start signal (CSTR) was turned ON by the PLC

while the actuator was moving, and duplication of move commands occurred

as a result.

20D STP signal OFF

This error indicates that the pause signal (*STP) was turned OFF by the PLC

while the actuator was moving, and the actuator became no longer movable

as a result.

20E Soft limit exceeded

This error indicates that a move command to outside the soft limit range was

issued while the actuator was moving.

211 HOME signal ON

This error indicates that the home return signal (HOME) was turned ON by

the PLC while the actuator was moving, and duplication of move commands

occurred as a result.