Parameter: 1 (reads electric energy) • function, Command/response, Example – Yokogawa PR300 Power and Energy Meter User Manual

Page 121

Advertising
background image

8-6

<Toc> <Ind>

<8. PR201 Original Communication Protocol>

IM 77C01E01-10E

Parameter: 1 (Reads electric energy)

• Function

Reads the active energy.

• Command/response

Number

of bytes

1

2

1

2

2

1

1

Command

element

STX

DG

1

Station

number

(ADR)

Checksum ETX

CR

There is no command data for data reading.

1

2

1

2

5

Response

element

STX

DG

1

Station

number

(ADR)

ٗٗٗٗٗ

2

1

1

Checksum ETX

CR

Number

of bytes

Response data is returned as a 5-byte ASCII character string (00000 to 99999).

• Example

Reads the active energy of PR300 with station number 01.

ᮀᮀ

indicates the checksum

value.

[Command]

[STX]DG101

ᮀᮀ

[ETX][CR]

Returns a response with the active energy of 10000 kWh for the above command.

[Response]

[STX]DG10110000

ᮀᮀ

[ETX][CR]

NOTE

Display ranges of active energy vary depending on the values of the VT and CT ratios. See
the following table for display range details.

Secondary rated power x VT ratio x CT ratio

100 kW or less

100 kW or more, 1 MW or less

1 MW or more, 10 MW or less

10 MW or more

Internal data

99999 kWh

999999 kWh

9999999 kWh

99999999 kWh

PR201 original communication display range

99999 kWh

NOTE

The secondary rated power of the PR300 changes depending on its model and suffix
codes.