<3. Procedures for Setting PR300 Functions>

IM 77C01E01-10E

3.5

Communication Setting

3.5.1

Protocol

[Procedure]

(1)

Write a protocol value to the D register in the table below. The data type is integer.

(2)

After writing that value, write 1 to the RS-485 writing status register, D0277.

D Register

D0271

D0277

Reference No.

40271

40277

H No.

010E

0114

Description

Protocol

RS-485 writing status
(D0271 to D0276 are
validated)

Effective Range

0: PC link
(without checksum)
1: PC link
(with checksum)
2: Modbus/ASCII
3: Modbus/RTU
4: Modbus/TCP *

1

5: PR201 original

If other than 1: Invalid
If 1: Writing is executed

Initial value of protocol: 1 (PC link with checksum)
*1: Modbus/TCP can be selected for the PR300 with Ethernet communication function only.

NOTE

When Modbus/TCP is selected for the protocol, the baud rate, the stop bit, the data
length and the station number are fixed and unchangeable.

When PR201 original is selected, the baud rate, the parity, the stop bit and the data
length cannot be set via communication.

[Example]

To set the protocol to 4 (Modbus/TCP):

For station number 01, use PC link communication (without checksum) and the random
write command as shown below:

[Command]

[STX]01010WRW02D0271,0004,D0277,0001[ETX][CR]

[Response]

[STX]0101OK[ETX][CR]